Home / Industry Knowledge / Custom Heating Elements

Resistance Heater Electrical Calculations for RFQs

Use voltage, power, current and resistance relationships correctly when specifying single-phase and three-phase resistance heaters.

Electrical relationships help check a heater RFQ, but the formula must match the circuit. A single resistive element, several parallel heaters and a three-phase bank can have the same total power while using different current and resistance values.

Use this guide to prepare a design review or RFQ. Final ratings depend on the complete product, installation, controls and operating environment.

Selection inputs that change the design

DecisionInformation to provideWhy it matters
Single resistive loadP = V × I and R = V² / PChecks rated current and hot resistance basis.
Parallel elementsEach branch sees supply voltageBranch currents add at the supply.
Series elementsSupply voltage divides by impedanceOne open element interrupts the path.
Three-phase bankConnection and line voltage matterDelta and wye use different element voltage.

Name the voltage at the element

State supply voltage, phase and whether the quoted voltage is line-to-line, line-to-neutral or across each element. Draw the intended connection for multi-element banks.

Do not calculate element resistance from total three-phase power without first identifying delta or wye connection and element count.

Separate rated values from measured values

Resistance wire changes with temperature, and meter accuracy plus lead resistance affects low-ohm measurements. The quotation should state whether resistance tolerance is referenced cold.

Current measured in service also reflects actual supply voltage and control modulation. Compare values under a defined stable condition.

Coordinate circuit protection and control

Provide total current, branch current, switching method and number of control stages to the electrical designer. Account for conductor, terminal and enclosure temperature.

Protective devices and grounding must follow the finished equipment design and applicable electrical requirements; heater formulas alone do not size the whole system.

Common specification mistakes

  • Using line voltage as element voltage without checking connection
  • Confusing total bank resistance with one element
  • Expecting cold and hot resistance to be identical
  • Sizing controls from nominal power only

RFQ checklist

  1. Supply voltage and frequency
  2. Single- or three-phase connection diagram
  3. Total and per-element power
  4. Expected current and resistance tolerance
  5. Control stages, switching and protection interface

Review the matching Custom Heating Elements product range, then send this checklist with your drawing for an engineer-reviewed quotation.

Frequently asked questions

How do I calculate current for one heater?

For a primarily resistive single load at its rated voltage, divide power by voltage.

How do delta and wye differ?

In delta each element is connected across line voltage; in wye each balanced element sees line voltage divided by the square root of three.

Why does measured resistance differ from the label?

Temperature coefficient, measurement leads, tolerance and the distinction between one element and the assembled circuit can all matter.